2.3 Connection Method
31
Fundamental of DIII-NET
[Bad Example 4]
[Bad Example 5]
[Bad Example 6]
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
Centralized
Controller
VRV Outdoor unit
VRV Indoor unit
F1 F2
F1 F2
Connect the
centralized controller
to the outdoor-outdoor
connection.
Connecting directly in the middle of indoor F1 or F2
line, without using F1 or F1 terminal, is prohibited.
Connect outdoor units without branch connection.
Indoor-outdoor
connection
Connect indoor units and outdoor units without branch connection.
Outdoor-outdoor
connection
Centralized
Controller
missmatch
VRV Outdoor unit
Refrigeront piping
VRV Indoor unit
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
F1 F2
F1 F2
Main
System A
2-00
~
2-03
2-00
2-01
2-02
2-03
1-00
1-01
1-02
1-03
Sub
NO!
2-00
~
2-03
1-00
~
1-03
System B
Conflict
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
Summary :
2.3 Connection Method 31 Fundamental of DIII-NET [Bad Example 4] [Bad Example 5] [Bad Example 6] IN/OUT F1 F2 OUT/OUT F1 F2 IN/OUT F1 F2 OUT/OUT F1 F2 Centralized Controller VRV Outdoor unit VRV Indoor unit F1 F2 F1 F2 Connect the centralized controller to the outdoor-outdoor connection.