28 00 00 ELECTRONIC SAFETY AND SECURITY
June 16, 2009
23
2)
White for voice cables.
3)
White for security cables except for direct burial cables.
C.
Minimum Conductor and Cable Types and Sizes
1. Low Voltage Power Cable
a. 18 AWG, stranded, insulated, and jacketed.
2. Card Reader Cable
a. 22 AWG (6 conductors minimum), stranded, shielded, insulated, and jacketed.
3. Keypad Cable
a. 18 AWG (6 conductors minimum), stranded, insulated, and jacketed.
4. Alarm Point Monitoring Cable
a. 20 AWG (4 conductors minimum), stranded, insulated, shielded and jacketed.
5. Siren, Speaker, and Control Point Cable
a. 18 AWG, stranded, insulated, and jacketed.
6. Camera Coaxial Cable
a. RG-59U Coaxial Cable with 75 Ohm Solid Copper Center Conductor and dual braid shield.
b. Coaxial cables with copper coated steel center conductors shall not be acceptable.
c. Coaxial cable connectors shall consist of three-piece crimp BNC connectors.
PART 3 - EXECUTION
3.1
COORDINATION
A.
Security contractor shall be required to coordinate installation activities with the following divisions or
groups:
1. Door hardware, doors and door frames by contractor.
2. Electrical power and pathways by contractor.
3. Telecom voice and data cabling and outlets by contractor.
4. Fire alarm interface by contractor.
5. Elevator demarc panel, traveling cables and elevator car card reader enclosure by contractor.
6. IP and phone number assignment by ITS.
7. Security system programming by ITS security operations.