Crestron Lighting Design Guide - 230V
DOC. 4859
54
sets the slab mode. Intended for heat-cool style systems, with slab connection on terminal W1,
space heat on terminal W2, and space cool on terminal Y1.
SLAB 5B:
Same as SLAB 5A, but for heat pump space systems, with slab heat on terminal W1,
and space heat/cool on terminals Y1/O/G. Aux heat is on terminal W2.
Sensor Products
The
CHV-RTHS
is a wall-mounted remote temperature and relative humidity sensor.
Using CAT5 or similar low-capacitance wire, the remote sensor may be mounted up to
152 m from the thermostat. One-piece mounting and a single non-polarized twisted-pair
connection make the CHV-RTHS simple to install. The 3.81 cm diameter face protrudes
just 0.32 cm from the wall surface and is easily painted or wallpapered to blend into the
wall surface. Up to two CHV-RTHS sensors may be connected to a single CHV-TSTAT
or CHV-THSTAT thermostat.
The
CHV-RTS
is a wall-mounted remote temperature sensor designed for use with select
Crestron thermostats. Using CAT5 or similar low-capacitance wire, the remote sensor may
be mounted up to 152 m from the thermostat. One-piece mounting and a single non-
polarized twisted-pair connection make the CHV-RTS simple to install. The 3.81 cm
diameter face protrudes just 0.32 cm from the wall surface and is easily painted or
wallpapered to blend into the wall surface. Up to four CHV-RTS sensors may be
connected to a single CHV-TSTAT or CHV-THSTAT thermostat.
The
C2N-RTHS
is a wall-mounted temperature and relative humidity sensor that
communicates directly with any 2-Series control system via the Cresnet control network
(not connected to the Crestron thermostats). One-piece mounting makes the C2N-RTHS
simple to install. The 3.81 cm diameter face protrudes just 0.32 cm from the wall surface
and is easily painted or wallpapered to blend into the wall surface.
The
CHV-RSS
is a remote temperature sensor designed for use with select Crestron
thermostats. Ideally suited for concrete slab, under floor, or any outdoor installation, the
CHV-RSS is an extremely accurate temperature sensor potted within a rugged waterproof
stainless steel sleeve. Using CAT5 or similar low-capacitance wire, the remote sensor may
be mounted up to 152 m from the thermostat. One-piece mounting and a single non-
polarized twisted-pair connection make the CHV-RSS simple to install. Up to four CHV-
RSS sensors may be connected to a single CHV-THSTAT or CHV-TSTAT thermostat.
Sensor Mounting - CHV-RTS and CHV-RTHS
NOTE:
Crestron strongly recommends low-capacitance
twisted pair wire such as CAT3 (up to 76 m) or CAT5 (up to
152 m) network cable when using remote sensors.
Maximum distance from sensor to thermostat is 150 m.
If multi-conductor cables are used, the leftover conductors
must NOT be used for other purposes and must be left
unconnected at both ends.
In situations where ordinary two-conductor thermostat wire
has been installed, it may be used for runs up to 30 meters).
This is not a preferred method of installation.
Other cable types are satisfactory, provided the total
capacitance is less than 7000 pF.