UFC 3-520-01 Interior Electrical Systems

Document source : artikel-software.com


UFC 3-520-01
June 10, 2002
11-5
Figure 11-3. Optimal Installation of Surge Protector Leads ­ Second Example

11-3.1.4 The installation instructions provided by some manufacturers specify that the
surge protector should be installed within 3 meters (10 feet) of the circuit connection
point. This long of a lead length is unacceptable because the allowed let-through
voltage would be too large to protect the downstream equipment. This effect applies to
all parallel surge protectors, regardless of rating and quality. Figure 11-4 shows an
example of a surge protector that is located on the other side of a room from the load
center; in this case, the surge protector provides no meaningful protection against
surges. Figure 11-5 shows another poor installation in which a safety switch is installed
between the surge protector and the breaker panel. Although the safety switch
application is well-intended, its use adds several feet of cable between the surge
protector and the breaker panel. In summary, the best surge protector will be rendered
useless by installing long leads between it and the circuit connection point.







Summary :

Optimal Installation of Surge Protector Leads ­ Second Example 11-3.1.4 The installation instructions provided by some manufacturers specify that the surge protector should be installed within 3 meters (10 feet) of the circuit connection point.


Tags : surge,protector,figure,between,installation,shows,breaker,safety,switch,example,leads,connection,circuit





Terms    |    Link pdf-search-files.com    |    Site Map
   |    Content Removal Notice   
   |    Contact   

All books are the property of their respective owners.
Please respect the publisher and the author for their creations if their books copyrighted